![]() ![]() Issue: When logging into a PL SCADA session using a remote desktop connection (mstsc admin) the Runtime. I am getting software protection failures on some of my Citect 6. NOTE: Assigning a static IP address to the server would eliminate future modifications as the server IP address remains constant and not change in case the server is rebooted. Citect Scada Software Protection Failure. If server has multiple NIC cards, each IP Address assigned to a NIC Card needs to be added seperately to the project. Assign an IP address that matches the server IP address. In Citect Project Editor select Network Addresses (Servers menu). ![]() ![]() A correct project setting would have Server and Control Client enabled and selected. Running Computer Setup Wizard on the server, indicated that the server role could only be a Client machine. While there are several reasons, in this case the problem was that the server IP address did not match the IP address assigned in Scada project. Once the Scada project runs, the following message appears and none of the devices are communicating: Scada server was rebooted after Windows Updates were applied. ![]()